USE

Hot-water heating systems
Domestic and commercial buildings.The electronic controls allows for setting advanced features

Wet rotor high efficiency circulator, driven by a permanent magnets synchronous motor (PM motor) controlled by an on board inverter.
The motor is protected against overload thanks to a thermal protection and an automatic electronic release function of the rotor.
No external protection is required.
Operated by selector technology.
ErP 2009/125/EC Standard.
Automatic speed control system able to adapt to the changing needs of the system. The circulator delivers the performance you need with minimum energy consumption
Automatic unlocking programme
Automatic detection of air

3 modes : Proportionnal differential pressure, constant differential pressure or fixed speed between min-max.

Conditions of use:
  • maximum pressure : 0,7 Mpa (7 bar)
  • Ambient temperature 2° to 40°C
  • Liquid temperature 2° to 95°C
  • Liquid temperature at 30°C ambiant : 30° à 95°C
  • Liquid temperature at 35°C ambiant : 35° to 90°C
  • Liquid temperature at 40°C ambiant : 40° to 70°C
  • Minimum pressure on the intake opening at 50°C : 0,03 MPa (0,03 bar)
  • Minimum pressure on the intake opening at 70°C : 0,10 MPa (1 bar) à 95°C
  • Maximum relative humidity : 95%
  • Approved fluids : Water for heating according to VDI 2035. Mixtures of water and glycol with glycol percentages not greater than 30%.
Pump housing : Cast iron EN-GLJ-200 with cataphoretic coating(KTL)
Impeller : Composite />Shaft : Ceramic
Bearing : Carbone
Thrust bearing : Ceramic
Rotor can : composite
Three modes
P - Proprotionnal pressure : The pressure level reduces according to the reduction of the heat requested by the system (reduced flow)
Particularly suitable for one or two pipes systems, application with variable pipe system cruve
C - Constant differential pressure : The circulator maintains a constant pressure level upon the decreasing demand for heat from the system.(reduced flew rate).
Suitable for underfloor heating systems, application with constant pipi system curve
Min-Max : The speed is fixed by positioning the regulator between the min and max position.
Suitable to any installation system, ensure optimum performance.